SRC - ECA approved Low Intensity Continuous Radiant Heating System Heater - UK Heater
| SRC 10 | SRC 15 | SRC 20* | SRC 25* | SRC 30* | |
|---|---|---|---|---|---|
| Technical Specification | |||||
| Burners / Branch - Max. | 6 | 5 | 4 | 3 | |
| Heat Input, kW Hs | 10 | 15 | 20 | 25 | 30 |
| Heat Input, kW Hi | 9 | 13.5 | 18 | 22.5 | 27 |
| Radiant Tube Length m - Min. | 3.0 | 5.2 | 6.0 | 7.2 | 8.6 |
| Between Burners m - Max. | 6.0 | 9.0 | 12.0 | 15.0 | 18.0 |
| Burner Weight - Kg | 9.5 per Burner | ||||
| Tubing - Kg/m | 4.3 with Reflectors | ||||
| Gas Connection | All Models R -1/2 | ||||
| Supply Pressure | Natural Gas - 20mbar; Propane - 37mbar | ||||
| Electrical Supply | 230v~50hz | ||||
| Flue Diameter | All Models - 100mm Dia. or 150mm Dia. | ||||
| Mouting Height | |||||
| Installation Height - m | 2.5m | 3.0m | 3.5m | 4.0m | 4.5m |
| Minimum Clearances To Combustibles | |||||
| Above - A - mm | 150 | ||||
| Below - C - mm | 1500 | 1530 | |||
| Side - B & D - mm | 510 | 600 | 760 | 840 | 920 |